How the calculator works
- Heat loss
- The standard method HVAC designers use: for each surface, area ÷ R-value × the temperature difference, plus the air that leaks out. The heater has to replace that heat to hold the temperature.
- Walls and ceiling
- Uninsulated stud wall with siding: R-3.5. Insulated 2×4 wall: R-12 including the studs. Uninsulated ceiling: R-3. Insulated ceiling: R-24 including the joists. These are typical values; yours may differ.
- Garage door
- Uninsulated steel door: U-1.15, the code default. Insulated: U-0.26, a tested polyurethane-filled steel door.
- Slab
- Heat lost through the edge of the concrete floor: 1.36 BTU/h per foot of exposed edge per °F, the Manual J figure for an uninsulated slab on moist soil.
- Air leaks
- Sealed 0.5, average 1 and drafty 2 air changes an hour, × 0.018 BTU per cubic foot per °F. Garages vary a lot here; these are our assumptions.
- Heater size
- Watts = BTU/h ÷ 3.412, rounded up to a common heater size. Circuit: the heater's current × 125%, because a heater is a continuous load.
Questions people ask
What size heater do I need for my garage?
It depends less on floor area than on how much heat the garage loses: insulation, the garage door, air leaks and how cold it gets outside. An uninsulated 2-car garage (24 × 24 ft, 9 ft ceiling) held at 50°F on a 15°F day loses about 26,600 BTU an hour, so it needs about 7,800 W of electric heat. Insulate the walls, ceiling and door and the same garage needs about 3,500 W.
What breaker does a 240 V garage heater need?
Heaters are a continuous load, so the circuit is sized at 125% of the heater's current. A 5,000 W heater draws about 21 A on 240 V, so it needs a 30 A circuit; a 7,500 W heater draws about 31 A and needs a 40 A circuit; 10,000 W needs a 60 A circuit. Have an electrician check the wire size and your panel.
Does insulating the garage door make a difference?
Yes. An uninsulated steel door loses heat roughly four times as fast per square foot as a tested insulated one, and a double door is over 100 square feet. Weatherstripping the bottom and sides also cuts air leaks, which are a large share of the load in most garages.
Can I heat a garage with a 120 V space heater?
Only a small, insulated one, or a corner of a bigger one. A plug-in heater on a normal outlet is limited to about 1,500 W, which is 5,118 BTU an hour. Most garages need 4,000 W or more, which means a 240 V heater on its own circuit.